INSTALLATION AND OPERATING INSTRUCTIONS
SC-3 Controller
MODULAR BOILER CONTROLLER SERIES
FOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTS
SC-3 Applications
Space Heat Systems With Outdoor Reset
Constant Temperature Setpoint Control
If your system is different than the above, call the Slant/Fin
technical services group at 800-873-4346 to
determine the proper control.
Controller Packing List
1- SC-3 Modular Controller P/N 435081
1- Outdoor sensor with enclosure P/N 339070
1- Universal sensor P/N 339071
The SC-3 is a microprocessor control which will sequence up to
three heating stages based on outdoor air temperature and supply
water temperature. Designed to handle a Caravan gas-fired,
oil-fired or *dual fuel-fired hot water heating plant for space
heating or “Setpoint” operation. A large easy to read display
provides current system temperatures and operating status.
ADDITIONAL FUNCTIONS INCLUDE:
Pump exercising. Pump purging. Boiler demand for space heating
loads. Set point demands for set point loads. Test sequence to
ensure proper component operation. CSA C US certified. Setback
input for energy savings.
SPACE HEATING OPERATION: When the outdoor air tempera-
ture drops below a preset value, the heating system is energized.
The SC-3 Controller determines the number of stages required to
meet the space heating needs and fires them. During operation,
the Controller scans system temperatures, adding or deleting
stages as necessary to satisfy heating load.
CONTENTS
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
a) Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
b) Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
c) View of Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
d) System Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Select System Type . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
A. Space Heating Only with Outdoor Reset . . . . . . .12
a) Dip Switch Settings . . . . . . . . . . . . . . . . . . . . . .12
b) Functions and Defaults . . . . . . . . . . . . . . . . . . . .13
c) Adjusting the Settings . . . . . . . . . . . . . . . . . . . . .13
B. Space Heating Only w/Setpoint Control . . . . . . . .17
a) Dip Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . .17
b) Functions and Defaults . . . . . . . . . . . . . . . . . . . . . .18
c) Adjusting the Settings . . . . . . . . . . . . . . . . . . . . . . .20
Viewing the Performance . . . . . . . . . . . . . . . . . . . . . . . . .22
Useful Hints and Reloading Factory Defaults . . . . . . . .23
Testing the Contol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Factory Default Listings . . . . . . . . . . . . . . . . . . . . . . . . . .28
SETPOINT OPERATION:
The SC-3 adds and deletes stages to minimize the difference
between the desired Setpoint temperature and the actual
measured Supply Water Temperature.
Dual-Fuel
* Not available in Canada
Printed in U.S.A. 605 PUBLICATION SC-3-40
Part No. 435083000
Seitenansicht 0
1 2 3 4 5 6 ... 26 27

Inhaltsverzeichnis

Seite 1 - SC-3 Controller

INSTALLATION AND OPERATING INSTRUCTIONSSC-3 ControllerMODULAR BOILER CONTROLLER SERIESFOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTSS

Seite 2 - INSTALLATION

11 SC-3 ControllerUser InterfaceThe control uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to se

Seite 3

SC-3 Controller 12GeneralThe DIP switch settings on the control are very important and should be set to the appropriate settings prior to making any a

Seite 4 -  ˚F ˚C  ˚F ˚C  ˚F ˚C 

13 SC-3 ControllerSPACE HEATING ONLY WITH OUTDOOR RESETAdvanced / InstallerThe Adv / Installer DIP switch selects the access level of the control. In

Seite 5 - SC-3 Controller 6

SC-3 Controller 14Boost - The amount of morning boost.Press the Menu button until ADJUST is visible on the top line of the display. Press the Item but

Seite 6 - WIRING THE SYSTEM

15 SC-3 ControllerBoiler Maximum - The maximum allowed boiler target temperature. Set at least 10˚F above Boiler Designsetting.Press the Menu button u

Seite 7 - SC-3 Controller 8

SC-3 Controller 16Setpoint Occupied - The minimum supply temperature when a setpoint demand is present during the Occupied period. This item is only a

Seite 8 - 9 SC-3 Controller

17 SC-3 ControllerGeneralThe DIP switch settings on the control are very important and should be set to the appropriate settings prior to making any a

Seite 9 - DISPLAY:

SC-3 Controller 18Advanced / InstallerThe Adv / Installer DIP switch selects the access level of the control. In the Installer access level, a limited

Seite 10 - SELECT SYSTEM TYPE:

19 SC-3 ControllerSetpoint operation is only available when DHW MODE is set to OFF. Since DHW MODEis only available if BOILER 3 is set to OFF, DHW wil

Seite 11 - CONTROL SET UP

SC-3 Controller 20Setpoint Mode - Selects the Setpoint Mode of operation. This item is only available when DHW MODE is set to OFF.Press the Menu butto

Seite 12 - (18.5˚C)

3 SC-3 ControllerRemove the safety dividersfrom the wiring chamber bypulling them straight out of theirgrooves.The control can be mounted ona standard

Seite 13

21 SC-3 ControllerDisplay DescriptionDefault SettingNewSettingWWSD Occupied - The systems warm weather shut down temperature during the Occupied perio

Seite 14 - (93.5˚C)

SC-3 Controller 22VIEW THE PERFORMANCEFUNCTION DESCRIPTION STEPSOUTDOORCurrent outdoor air temperature as measured by the outdoor sensor.Press the Men

Seite 15 - (15.5˚C)

23 SC-3 ControllerUSEFUL HINTSHint #1Reloading Factory DefaultsTo reload the factory defaults, power down the control for 10 seconds. Power up the con

Seite 16

SC-3 Controller 24TESTING THE CONTROLThe control has a built-in test routine that is used to test the main control functions. The control continually

Seite 17 - Rotate / Off

25 SC-3 ControllerError MessagesThe control was unable to read a piece of information stored in its memory. Because of this, thecontrol was required t

Seite 18

SC-3 Controller 26The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise

Seite 19 - Default

27 SC-3 ControllerNOTES

Seite 20

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontariowww.slantfin

Seite 21 - VIEW THE PERFORMANCE

SC-3 Controller 4MOUNTING THE SENSORNote: The temperature sensor (thermistor) is built into the enclosure.• Remove the screw and pull the front cove

Seite 22 - USEFUL HINTS

5 SC-3 ControllerWIRING AND TESTING THE SENSORWARNING: Do not run sensor wires close to and parallel to telephone or power cables. If the sensor wires

Seite 24 - Error Messages

7 SC-3 ControllerWIRING THE SYSTEMUse one of the following wiring diagrams to wire your system, along with the appropriate diagram on page 9.1. Gas fi

Seite 25

SC-3 Controller 82. Oil fired - Space Heating onlyNOTE: For boiler termination wiring at modules, see page 9

Seite 27

SC-3 Controller 10Symbol DescriptionStageDisplays which stage relays are turned on.PumpDisplays when the primary pump relay is turnedon.˚F, ˚C, min, h