Gas Conversion Field Assembly Kit
Natural Gas to Liquefied Petroleum (Propane) or
Liquefied Petroleum (Propane) Gas to Natural
Only for use with Slant/Fin boilers equipped with Honeywell VR8200, VR8204, VR8300 and
VR8304 gas valves, either standing (continuous burning) pilots or intermittent ignition
systems.
WARNING
This conversion kit shall be installed by a
qualified service agency in accordance with
the manufacturers instructions and all
applicable codes and requirements of the
authority having jurisdiction. If the informa-
tion in these instructions is not followed
exactly, a fire, an explosion or production of
carbon monoxide may result causing prop-
erty damage, personal injury or loss of life.
The qualified service agency is responsible
for the proper installation of this kit. The
installation is not proper and complete until
the operation of the converted appliance is
checked as specified in the manufacturers
instructions supplied with the kit.
WARNING-IMPORTANT
1. This conversion kit is supplied with the
same parts normally provided on
SLANT/FIN factory built boilers which are
Design Certified by CSA International.
However, because we have no way of
applying our own quality control procedures
to field alterations made by others on this
boiler, these alterations are not the respon-
sibility of SLANT/FIN. These alterations are
the responsibility of the installer of this con-
version kit. The instructions below must be
carefully followed in order to duplicate
factory installation.
2. The installation must conform to the require-
ments of the authority having jurisdiction or,
in the absence of such requirements, to the
National Fuel Gas Code ANSI Z223. 1-lat-
est edition.
The boiler warranty is void unless this field assembly conversion kit has been properly installed,
labels completed and applied to boiler and registration card completed and received
by Slant/Fin within 10 days after kit has been installed in boiler.
PUBLICATION No. GCK-40
Part No. 46-0527
Printed in U.S.A. 708
WARNING
LIQUEFIED PETROLEUM (L.P.) PROPANE GAS-
FIRED BOILER LOCATION
REQUIRES SPECIAL ATTENTION
Liquefied Petroleum (LP) propane gas is heavier
than air. Therefore, propane boilers, piping, valves
must NOT be installed in locations where propane
leaking from defective equipment and piping will
"pool" in a basement or other space below the leak.
A spark or flame from the boiler or other source
may ignite the accumulated propane gas causing
an explosion or fire. Provide a level, solid founda-
tion for the boiler. Location should be as near the
chimney as possible so that the flue pipe from boil-
er to chimney is short and direct.
THE UNIFORM MECHANICAL CODE may be in
effect in your geographic area.
The following precautions are cited by the 1994
UNIFORM MECHANICAL CODE, section 304.6:
"LPG Appliances. Liquefied petroleum gas-
burning appliances shall not be installed in a pit,
basement or similar location where heavier-
than-air gas might collect. Appliances so fueled
shall not be installed in an above-grade under-
floor space or basement unless such location is
provided with an approved means for removal of
unburned gas."
Consult Chapter 5 of the 1994 UNIFORM
MECHANICAL CODE for design criteria of the
"approved" means for removal of unburned gas.
Seitenansicht 0
1 2 3 4 5 6 ... 19 20

Inhaltsverzeichnis

Seite 1 - Printed in U.S.A. 708

Gas Conversion Field Assembly KitNatural Gas to Liquefied Petroleum (Propane) orLiquefied Petroleum (Propane) Gas to NaturalOnly for use with Slant/Fi

Seite 2 - Front and Right End View

10Wiring Diagrams- Victory II - VH, VHL Series

Seite 3 - Base Assembly

11Wiring Diagrams- Victory II - VHS, VHLS Series (Spark Ignition)

Seite 4 - RIGHT END VIEW

12Wiring Diagrams- Victory, VSP, VSPH

Seite 5

13WIRING DIAGRAM - GALAXY/SENTRY—CONTINUOUS (STANDING) PILOTCAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors c

Seite 6 - VICTORY V SERIES BOILER

14CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. “Verify proper

Seite 7 - INSTALLATION

15WIRING DIAGRAMS FOR SENTINEL HOT WATER BOILERSCAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause imp

Seite 8 - GAS LEAK TESTS

16Elevation - FeetV-60 thru V-180Sentry S-60 thru S-150 & SX-150 thru SX-210TABLE 1ORIFICE SIZE TABLESENTRY AND SENTINEL SERIESVICTORY SERIESGALAX

Seite 9

17TABLE 2INPUT RATING OF BOILERSNote: All models of the boilers will have the same input rating after converted.

Seite 10

18LIGHTING INSTRUCTIONSContinuous Burning Pilot (24V).FOR BOILERS EQUIPPED WITH GAS VALVES VR8200and VR8300.SAFETY INFORMATIONFOR YOUR SAFETY READ BEF

Seite 11

HONEYWELL IID SYSTEM .FOR BOILERS EQUIPPED WITH GAS VALVE VR8204 ORVR8304.SAFETY INFORMATIONFOR YOUR SAFETY READ BEFORE LIGHTINGA. This appliance is e

Seite 12

2SENTRY SERIES BOILERLocation and identification of parts.Base AssemblyFront and Right End View(Sentry “S” Series shown)BurnersPilotBurnerAccessDoorGa

Seite 13

GAS RATE TABLECubic FeetBoiler rated input Gas Consumptioncu. ft./hr. of 1000 Btu/cu. ft. 1000 Btu/cu.ft. gas, in 3Natural Gas minutes, at rated input

Seite 14

3VICTORY VSP AND VSPH SERIES BOILERSLocation and identification of parts.Base Assembly

Seite 15

4SENTINEL SERIES BOILERLocation and identification of parts.BurnersPilotBurnerAccessDoorGas ValveLEFT END VIEWRIGHT END VIEW

Seite 16

5VICTORY II SERIES BOILERLocation and identification of parts.VICTORY II - VHS, VHLS BASE ASSEMBLYLocation and identification of parts.PilotGas Manifo

Seite 17 - INPUT RATING OF BOILERS

6VICTORY V SERIES BOILERLocation and identification of parts.BurnersPilotBurnerAccessDoorGas ValvePressure/TemperatureGaugeAir FlowProving SwitchDraft

Seite 18 - To Turn Off Gas To Appliance

7GALAXY BOILERRemove front panel (Figure 1) by pressing handagainst panel and pushing up. Remove burner accessdoor (Figure 2) by removing 2 wing nuts,

Seite 19

8e) Install new pressure regulator adjustment screw until it is flush with the top of the casting.f) After e) above, turn adjustment screw clockwise a

Seite 20

9Wiring Diagram - Victory “V” Series BoilersCAUTION: Label all wires prior to disconnection when servicing controls.Wiring errors can cause improper